Three-dimensional Oil-immersedTransformer

Product Description Coil: It is made of high quality acal enameled round wire and flat copper wire. The coil of round structure has higher strength. Oil tank: The transformer adopts fully sealed structure, canceling the oil storage tank, because the way of oil and air contact is isolated, insulation is not easy to be damp, the aging degree is greatly reduced, the reliability and service life of the transformer are greatly improved. The whole surface of the oil tank is sprayed with plastic after rust prevention treatment, which has strong corrosion resistance and is beautiful and generous.

keyword:

Products Details

S11-M.RL Three-dimensional Oil-immersedTransformer
Rated Capacity
(kVA)
Rated primary voltage(kV) H.V. Tap range
(%)
Rated Secondary voltage(kV0) Connection  symbol No-load Loss
(kW)
On-load Loss
(kW)
 
No-load current
(%)
Short circuit impedance Weight
(KG)
L*W*H
(mm)
Gauge
(mm*mm)
30 6
6.3
10
10.5
11
±5
±2*2.5
0.4 Dyn 11
Yyn0
0.1 0.63/0.6 0.60  4.0  290 791*612*996 380*550
50 0.13 0.91/0.87 0.48  370 926*648*1034 380*550
63 0.15 1.09/1.04 0.46  430 1010*672*1064 380*550
80 0.18 1.31/1.25 0.44  480 1027*677*1094 380*550
100 0.2 1.58/1.5 0.42  505 899*791*1114 380*550
125 0.24 1.89/1.8 0.40  560 1007*872*1144 380*550
160 0.28 2.31/2.2 0.38  680 1117*967*1164 400*660
200 0.34 2.73/2.6 0.36  770 1145*991*1215 400*660
250 0.4 3.2/3.05 0.34  970 1241*1075*1190 400*660
315 0.48 3.83/3.65 0.30  1035 1180*1020*1250 550*820
400 0.57 4.52/4.3 0.30  1210 1311*1136*1235 550*820
500 0.68 5.41/5.15 0.30  1510 1404*1216*1368 550*820
630 Dyn 11
Yyn0
0.81 6.2 0.30  4.5  1820 1450*1255*1350 550*820
800 0.98 7.5 0.28  2100 1492*1297*1440 550*820
1000 1.15 10.3 0.28  2510 1662*1456*1437 550*1070
1250 1.36 12 0.26  3120 1750*1510*1580 550*1070
1600 1.64 14.5 0.24  3660 1855*1605*1610 550*1070
Note: 1. For transformers with rated capacities of 500kVA and below, the load loss values above the diagonal line in the table are applicable to Dyn11 coupling group, and the load loss values below the diagonal line are applicable to Yyn0 coupling group:
2. The size in the table is for reference only. The installation and design must be subject to the outline drawing provided by the company.

 

S13-M.RL Three-dimensional Oil-immersedTransformer
Rated Capacity
(kVA)
Rated primary voltage(kV) H.V. Tap range
(%)
Rated Secondary voltage(kV0) Connection  symbol No-load Loss
(kW)
On-load Loss
(kW)
No-load current
(%)
Short circuit impedance Weight
(KG)
L*W*H
(mm)
Gauge
(mm*mm)
30 6
6.3
10
10.5
11
±5
±2*2.5
0.4 Dyn 11
Yyn0
0.08 0.63/0.6 0.30  4.0  295 791*612*996 380*550
50 0.1 0.91/0.87 0.24  375 926*648*1034 380*550
63 0.11 1.09/1.04 0.23  435 1010*672*1064 380*550
80 0.13 1.31/1.25 0.22  485 1027*677*1094 380*550
100 0.15 1.58/1.5 0.21  510 899*791*1114 380*550
125 0.17 1.89/1.8 0.20  570 1007*872*1144 380*550
160 0.2 2.31/2.2 0.19  690 1117*967*1164 400*660
200 0.24 2.73/2.6 0.18  820 1184*1025*1194 400*660
250 0.29 3.2/3.05 0.17  980 1241*1075*1190 400*660
315 0.34 3.83/3.65 0.16  1045 1180*1020*1250 550*820
400 0.41 4.52/4.3 0.16  1295 1333*1154*1272 550*820
500 0.48 5.41/5.15 0.15  1520 1404*1216*1368 550*820
630 Dyn 11
Yyn0
0.57 6.2 0.15  4.5  1830 1450*1255*1350 550*820
800 0.7 7.5 0.15  2290 1555*1347*1426 550*820
1000 0.83 10.3 0.14  2620 1605*1422*1606 550*1070
1250 0.97 12 0.13  3150 1750*1510*1580 550*1070
1600 1.17 14.5 0.12  3755 1846*1599*1638 550*1070
Note: 1. For transformers with rated capacities of 500kVA and below, the load loss values above the diagonal line in the table are applicable to Dyn11 coupling group, and the load loss values below the diagonal line are applicable to Yyn0 coupling group:
2. The size in the table is for reference only. The installation and design must be subject to the outline drawing provided by the company.

 

Product Description

Coil: It is made of high quality acal enameled round wire and flat copper wire. The coil of round structure has higher strength.

Oil tank: The transformer adopts fully sealed structure, canceling the oil storage tank, because the way of oil and air contact is isolated, insulation is not easy to be damp, the aging degree is greatly reduced, the reliability and service life of the transformer are greatly improved. The whole surface of the oil tank is sprayed with plastic after rust prevention treatment, which has strong corrosion resistance and is beautiful and generous.

Product Feature

Magnetic circuit balance
The three-phase magnetic circuit length of the three-dimensional coil core is equal and the shortest, so the magnetic circuit is balanced.
Lower losses
The three-dimensional coil iron core has no joints and no high magnetic area, and the magnetic flux direction is consistent with the grain orientation of the iron core material, which gives full play to its high magnetic permeability characteristics and greatly reduces no-load loss and no-load current.
Less noise
The silicon steel strip of the single frame is closely connected, and the three single frames are spliced and solidified into an overall structure. The iron core is a closed structure, and the magnetic circuit is coherent and has no air gap, so that the noise is minimized.
Strong resistance to short circuit
The winding section is circular, the force is consistent, and the compression resistance is strong when the short circuit electric power is applied. The clamping part is a welded triangular overall structure with high stability and high overall strength.

 

Related Products

undefined

undefined

Inquiry Now

Complete the form to get more information soon

Welcome to leave your information to get contact with us!

%{tishi_zhanwei}%

Add

Jikai Electric Power Technology Industrial Park,Baoding City, Hebei Province, China.

Share our website


Copyright © 2022  Baoding Jikai Power Equipment Co., Ltd.  All Rights Reserved.  

Business license