On-load Voltage Regulation Distribution Transformer

keyword:

Products Details

SZ11- On-load Voltage Regulation Distribution Transformer
Rated Capacity
(kVA)
Rated primary voltage(kV) H.V. Tap range
(%)
Rated Secondary voltage(kV0) Connection  symbol No-load Loss
(kW)
On-load Loss
(kW)
No-load current
(%)
Short circuit impedance Weight
(KG)
L*W*H
(mm)
Gauge
(mm*mm)
200 6
6.3
10
10.5
11
±5
±2*2.5
0.4 Dyn 11
Yyn0
0.38 2.9 1.00  4.0  1140 1700*850*1520 550*550
250 0.44 3.42 0.90  1280 1740*880*1560 660*660
315 0.53 4.1 0.90  1450 1780*920*1600 660*660
400 0.64 4.95 0.80  1650 1810*960*1650 660*660
500 0.76 5.89 0.80  2010 1910*1100*1800 660*660
630 0.96 7.26 0.60  4.5  2940 2190*1140*2050 660*660
800 1.12 8.89 0.60  3050 2250*1180*2060 820*820
1000 1.36 10.4 0.60  3210 2280*1220*2080 820*820
1250 1.56 12.3 0.50  3740 2400*1370*2150 820*820
1600 1.92 14.7 0.50  5150 2520*1500*2180 820*820
2000 2.27 18.6 0.40  5.0  5700 2600*1600*2200 1070*1070
2500 2.68 21.6 0.40  6300 2700*1720*2230 1070*1070

 

SZ13- On-load Voltage Regulation Distribution Transformer
Rated Capacity
(kVA)
Rated primary voltage(kV) H.V. Tap range
(%)
Rated Secondary voltage(kV0) Connection  symbol No-load Loss
(kW)
On-load Loss
(kW)
No-load current
(%)
Short circuit impedance Weight
(KG)
L*W*H
(mm)
Gauge
(mm*mm)
200 6
6.3
10
10.5
11
±5
±2*2.5
0.4 Dyn 11
Yyn0
0.304 2.9 1.00  4.0  1090 1600*80081500 550*550
250 0.352 3.42 0.90  1280 1680*830*1530 660*660
315 0.424 4.1 0.90  1450 1720*880*1580 660*660
400 0.512 4.95 0.80  1650 1790*920*1620 660*660
500 0.608 5.89 0.80  2010 1860*1050*1730 660*660
630 0.768 7.26 0.60  4.5  2940 2150*1100*1950 660*660
800 0.896 8.89 0.60  3050 2200*1130*2040 820*820
1000 1.088 10.4 0.60  3210 2250*1200*2050 820*820
1250 1.248 12.3 0.50  3740 2350*1300*21530 820*820
1600 1.536 14.7 0.50  4900 2420*1460*2170 820*820
2000 1.816 18.6 0.40  5.0  5420 2550*1550*2190 1070*1070
2500 2.144 21.6 0.40  6000 2620*1680*2210 1070*1070

 

Product Descripition

The no-load loss of transformer accounts for about 45% of the line loss of power system. Reducing the line loss is one of the main ways to improve the efficiency of power supply department. In the rural or suburban areas, due to seasonal changes, the load shows regular high and low changes, such as "coal to electricity" in the north, busy farming and idle farming, agricultural irrigation, etc. The on-load capacitor and voltage regulating transformer is an energy-saving transformer that can automatically distinguish and send a conversion signal through the on-load capacitor and voltage regulating switch to complete the capacity switching and tap gear conversion according to the changes in the output current and voltage of the secondary side. It is suitable for the rural grid and urban grid with large seasonal load changes. It is a new technology and new product promoted and applied by the State Grid Corporation.

Product Feature

t solves the problem of serious overload caused by "small horse-drawn carts" and high line loss caused by "big horse-drawn carts" that has plagued the power supply department for a long time.
Instead of "child and mother change", extend the replacement cycle, cover an area loss, save transformation investment.
The integration of regulating capacity and voltage can save energy and improve the quality of power supply.
The intelligent degree is high, and the monitoring data is provided to the distribution integrated management system and the power grid economic operation system, which is conducive to the construction of smart grid.

Related Products

undefined

undefined

Inquiry Now